EnOcean Equipment Profiles (EEP)
Which data an EnOcean sensor sends is defined by its equipment profile, the EEP. Here are the profiles our sensors send and our lighting controllers evaluate – with the EnOcean Alliance title and the matching devices.
How to read an EEP code
RORG-FUNC-TYPEAn EEP consists of three hexadecimal numbers. The first (RORG) names the telegram type, the second (FUNC) the basic function, the third (TYPE) the specific device variant. A5-07-01 is therefore a 4-byte telegram (A5) from an occupancy sensor (07) in the variant with supply voltage monitoring (01).
A receiver can only read the values if it knows the profile. That is why the EEP belongs in every specification and on every data sheet.
| RORG | Short name | Meaning |
|---|---|---|
| F6 | RPS | Repeated Switch Communication – push buttons and switches |
| D5 | 1BS | 1 Byte Communication – simple contacts |
| A5 | 4BS | 4 Byte Communication – most sensors |
| D2 | VLD | Variable Length Data – 1 to 14 bytes, multisensors |
| D1 | MSC | Manufacturer Specific Communication – manufacturer profiles |
All EnOcean Alliance profiles
23 profiles| EEP | EnOcean Alliance title | What it transmits | Sent by | Evaluated by |
|---|---|---|---|---|
| A5-02-05 | Temperature Sensors · Temperature Sensor Range 0°C to +40°C | Temperature | EnoSense® Wall+Desk | – |
| A5-04-01 | Temperature and Humidity Sensor · Range 0°C to +40°C and 0% to 100% | Temperature, humidity | EnoSense® Wall+Desk | – |
| A5-04-03 | Temperature and Humidity Sensor · Range -20°C to +60°C 10bit-measurement and 0% to 100% | Temperature, humidity (10 bit) | EnoSense® Temp/RH EnoSense® RADON EnoSense® Wall+Desk | – |
| A5-06-01 | Light Sensor · Range 300lx to 60.000lx | Illuminance, supply voltage | EnoSense® LUX | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
| A5-06-02 | Light Sensor · Range 0lx to 1.020lx | Illuminance, supply voltage | EnoSense® Wall+Desk | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
| A5-06-03 | Light Sensor · 10-bit measurement (1-Lux resolution) with range 0lx to 1000lx | Illuminance (10 bit) | EnoSense® LUX EnoSense® Wall+Desk | – |
| A5-07-01 | Occupancy Sensor · Occupancy with Supply voltage monitor | Motion or occupancy, supply voltage | EnoSense® PIR Ceiling EnoSense® PIR DOT EnoSense® Desk EnoSense® Desk VIB EnoSense® Window EnoPuck® CO2 EnoPuck® CO2 WALL EnoPuck® CO2 NOISE | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
| A5-07-02 | Occupancy Sensor · Occupancy with Supply voltage monitor | Motion, supply voltage | EnoSense® PIR DOT | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
| A5-07-03 | Occupancy Sensor · Occupancy with Supply voltage monitor and 10-bit illumination measurement | Motion, illuminance, supply voltage | EnoSense® PIR Ceiling EnoSense® PIR DOT | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
| A5-08-01 | Light, Temperature and Occupancy Sensor · Range 0lx to 510lx, 0°C to +51°C and Occupancy Button | Illuminance, temperature, occupancy | EnoSense® PIR Ceiling EnoPuck® CO2 NOISE | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
| A5-08-02 | Light, Temperature and Occupancy Sensor · Range 0lx to 1020lx, 0°C to +51°C and Occupancy Button | Illuminance, temperature, occupancy | EnoSense® PIR Ceiling | – |
| A5-08-03 | Light, Temperature and Occupancy Sensor · Range 0lx to 1530lx, -30°C to +50°C and Occupancy Button | Illuminance, temperature, occupancy | EnoSense® PIR Ceiling | – |
| A5-09-04 | Gas Sensor · CO2 Sensor | CO2, humidity, temperature | EnoSense® CO2 EnoPuck® CO2 EnoPuck® CO2 WALL EnoPuck® CO2 NOISE | BL-204-10-868 EVG FLEX |
| A5-12-00 | Automated Meter Reading (AMR) · Counter | Counter value – for the EnoSense® RADON, the radon concentration | EnoSense® RADON | – |
| A5-14-01 | Multi-Func Sensor · Single Input Contact (Window/Door), Supply voltage monitor | Window or door contact, supply voltage | EnoSense® Window | – |
| A5-14-05 | Multi-Func Sensor · Vibration/Tilt, Supply voltage monitor | Vibration or tilt, supply voltage | EnoSense® Wall+Desk | – |
| D2-14-40 | Multi Function Sensors · Indoor -Temperature, Humidity XYZ Acceleration, Illumination Sensor | Temperature, humidity, acceleration (X, Y, Z), illuminance Status at the Alliance: proposal | EnoSense® Wall+Desk | – |
| D2-14-41 | Multi Function Sensors · Indoor -Temperature, Humidity XYZ Acceleration, Illumination Sensor, Window Contact | as D2-14-40, plus window contact Status at the Alliance: not released | EnoSense® Wall+Desk | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
| D2-14-52 | Multi Function Sensors · Sound, Pressure, Illumination, Presence and Temperature Sensor | Sound level, illuminance, presence, temperature Status at the Alliance: not released | EnoPuck® CO2 NOISE | – |
| D2-14-59 | Multi Function Sensors · Temperature, Humidity, PM, CO2, HCHO and TVOC | Indoor air multisensor (temperature, humidity, CO2 and more) Status at the Alliance: not released | EnoSense® CO2 | – |
| D2-32-02 | A.C. Current Clamp · Type 0x02 | AC current, three channels | EnoSense® 3PH Current Sense | – |
| D5-00-01 | Contacts and Switches · Single Input Contact | Contact open or closed | EnoSense® Window EnoSense® Wall+Desk | – |
| F6-02-01 | Rocker Switch, 2 Rocker · Light and Blind Control - Application Style 1 | Rocker switch press sent by EnOcean push buttons from other manufacturers | – | BL-201-10-868 UP FLEX BL-204-10-868 EVG FLEX BL-205-10-868 MINI FLEX |
Manufacturer-specific profiles
RORG D1 · MSCFor some measurands there is no suitable Alliance profile. These devices send a manufacturer-specific telegram (MSC, RORG D1). The numbers after it are assigned by the manufacturer, not by the Alliance, and are only unique together with the manufacturer ID. A gateway needs the manufacturer’s description – the VL-700 BASE evaluates these profiles, and we provide the description for other systems.
| Code | What it transmits | Device |
|---|---|---|
| D1-07-0F | Count value (passages in both directions) | EnoSense® People Counter PRO |
| D1-07-10 | Count value (entries and exits), supply voltage | EnoSense® People Counter |
| D1-07-11 | Sound level, battery, solar and storage voltage | EnoSense® NOISE |
| D1-09-01 | CO2, humidity, temperature, energy state | EnoSense® CO2 |
| D1-09-08 | Particulate matter (PM), VOC index, temperature, humidity | EnoSense PM VOC |
| MSC | Presence and number of people in the detection area | EnoSense® Presence Count |
Frequently asked questions
5 questionsWhat is an EEP?
An EnOcean Equipment Profile describes how the data in an EnOcean radio telegram is structured: which bits carry which quantity and in what range. The profiles are defined by the EnOcean Alliance.
Where can I find a device’s EEP?
In the data sheet and on the product page, for our devices under “Device Profile (EEP)”. Some devices send several profiles, for example for different measurands.
What is the difference between 4BS and VLD?
4BS telegrams (A5) always carry 4 bytes of payload. VLD telegrams (D2) are 1 to 14 bytes long and can therefore carry more measurands at once, for example from multisensors.
How do I recognise a manufacturer-specific profile?
By the RORG D1 (MSC). Such profiles are not defined by the Alliance; the gateway needs the manufacturer’s description.
Does the gateway need to know the profile?
Yes, otherwise it cannot read the values. The VL-700 BASE evaluates the profiles of our sensors. For devices from other manufacturers, we check the profiles before the project.
As of October 2026. Titles verbatim from the EnOcean Alliance EEP Viewer, structure according to “EnOcean Equipment Profiles 3.1”. Device measuring ranges are on the product pages.