Building sensors: which sensors an office building needs
Which sensors an office building needs follows from the tasks, not from the catalogue. This guide leads from the task to the measured variable and the right sensor – with power supply, data path, sensor density and the questions to settle before the tender. The model floor shows what the finished plan looks like.
First the task, then the sensor
Six tasksNobody needs “sensors” as such. What is needed is ventilation that runs on demand, a room that can be booked when it is free, or evidence for occupational safety. If you write down the tasks first, the measured variables almost follow by themselves – and you avoid devices whose values nobody uses.
Which variable, which sensor
The overviewThe table assigns each task its measured variable, the type of sensor and our matching device – with the power supply as listed in the sensor overview. Device names lead to the product page, the second link to the use case or article.
| Task | Measured variable | Sensor type | Device and further reading | Power supply |
|---|---|---|---|---|
| Ventilate on demand | CO2, plus temperature and humidity | NDIR CO2 sensor on the wall, display in the room | EnoSense® CO2 EnoPuck® CO2 Use case: Ventilate by CO2 | EnoSense®: solar cell with backup battery · EnoPuck®: plug-in power supply 12 V DC |
| Air quality beyond CO2 | Particulate matter (PM1 to PM10), VOC index | Particle and VOC sensor | EnoSense® PM VOC Use case: Measure air quality | Plug-in power supply 12 V DC |
| Occupational safety on ground and basement floors | Radon | Radon sensor with ionisation chamber | EnoSense® RADON Know-how: Radon in the workplace | PoE or 12 to 48 V DC |
| Control the room climate | Temperature, relative humidity | Temperature and humidity sensor | EnoSense® Temp/RH | Battery CR2032 |
| Turn heating down while airing | Window open or closed | Magnetic contact on the window frame | EnoSense® Window | Battery CR2032 |
| Light and rooms by presence | Motion, presence | PIR motion detector on the ceiling | EnoSense® PIR Ceiling EnoSense® PIR DOT Use case: Lighting by presence | PIR Ceiling: solar cell with backup battery · PIR DOT: battery CR3032 |
| Use daylight | Illuminance in lux | Light sensor | EnoSense® LUX | Battery CR2032 |
| Make use of rooms and areas | People count, occupancy of an area | Counter above the door or ceiling sensor, no camera | EnoSense® People Counter EnoSense® People Counter PRO EnoSense® Presence Count Know-how: People counting without a camera | People Counter: 2 × AA · PRO: PoE, USB or 12 to 48 V DC · Presence Count: PoE |
| Share desks | Occupancy per desk | Motion at the desk or vibration under the desktop | EnoSense® Desk VIB EnoSense® Desk EnoSense® Wall+Desk Use case: Desk occupancy | Desk, Desk VIB: battery CR2032 · Wall+Desk: solar cell with backup battery |
| Acoustics in open areas | Sound pressure level | Sound sensor | EnoSense® NOISE EnoPuck® CO2 NOISE | EnoSense®: solar cell with 2 × AA · EnoPuck®: plug-in power supply 12 V DC |
| Energy per installation | Current, three-phase | Split-core current transformers | EnoSense® 3PH Current Sense Use case: Retrofit energy monitoring | Powered by its own current transformers |
Solar, battery, power supply or PoE
Power supplyA sensor needs energy for measuring and transmitting. How much depends on the variable: a window contact reports rarely and needs little, a CO2 sensor runs a measuring cell, a radon sensor an ionisation chamber. This leads to different types of power supply – and each one ends up in a different trade.
| Power supply | Examples from our range | What it means for planning |
|---|---|---|
| Solar cell with backup battery | EnoSense® CO2, PIR Ceiling, Wall+Desk, NOISE | No cable. Needs light at the mounting location; the battery bridges dark periods. |
| Battery | EnoSense® Temp/RH, LUX, Window, Desk, Desk VIB, PIR DOT, People Counter | No cable. Replace by condition, not by calendar; cell type and number belong in maintenance planning. |
| Plug-in power supply | EnoPuck® CO2, EnoPuck® CO2 NOISE, EnoSense® PM VOC | Plan a socket at the mounting location. |
| PoE | EnoSense® RADON, Presence Count, People Counter PRO, EnoDisc® receivers | Network cable and PoE switch belong in electrical and IT planning. |
| From the measurement | EnoSense® 3PH Current Sense | Powered by the current transformers that are clipped around the conductors anyway. |
The power supply is specified per device group, not per wireless standard. How long batteries last and when they are replaced is covered in detail under operation and maintenance.
Operation and maintenance: battery, signs of life, calibration →
Wireless or wired?
TransmissionWired sensors pay off where the cable is there anyway: in new buildings with a fixed room layout, or for devices that need mains power in any case. In existing buildings and on floors that change, wireless is usually the shorter route: no cable runs to the sensors, only to the receivers on the ceiling. This makes retrofitting possible during operation, and when the layout changes, the sensor simply moves along.
Our sensors transmit using EnOcean (ISO/IEC 14543-3-10), at 868.3 MHz in Europe. A telegram lasts about one millisecond – which is why a small solar cell is enough for many devices. The devices on PoE or a power supply also transmit their readings wirelessly; there the cable only provides power.
How EnOcean differs from Zigbee, LoRaWAN and Bluetooth LE, and when which standard fits, is covered in the comparison of wireless standards.
From the sensor to building automation
Data pathA reading passes four stations. For planning, the last one matters most: which language does the system speak that takes over the values?
| Station | Device | What happens |
|---|---|---|
| Measure | Wireless sensor | Measures and transmits – on change and additionally as a sign of life. |
| Receive | EnoDisc® on the ceiling, EnoDisc® 2 available soon | Picks up the telegrams within a planning radius of around 12 m and passes them on via Ethernet. |
| Evaluate | VL-700 BASE 2 gateway | Collects the values from up to 32 receivers and 500 sensors, evaluates them and keeps a history. |
| Hand over | MQTT, BACnet, KNX, Modbus TCP | Passes the values to building automation, dashboard or cloud – also via several routes in parallel. |
Depending on the manufacturer, the gateway is also called a sensor gateway, IoT controller or edge controller; the individual wireless sensors are often called sensor nodes. The gateway is where wireless telegrams become data points. If you run your own platform, you can also connect the EnoDisc® 2 directly to your own MQTT broker.
Which data path fits: MQTT, BACnet, KNX and Modbus TCP →
How many sensors does a floor need?
Sensor densityThe number of sensors follows from the measuring locations, not from the floor area alone. A meeting room is a measuring location of its own, however small; an open area is divided into zones. These guide values come from building standards and from our planning:
| What | Guide value | Source |
|---|---|---|
| CO2 in open areas | at least one monitor per 325 m² | WELL v2, Feature A08 |
| CO2 under RESET Air | one device per space type, at most 500 m² per device | RESET Air, Commercial Interiors |
| CO2 in meeting rooms | one sensor per room | separate measuring location, our planning |
| Display in the room | one per 325 m² | WELL v2, Feature A08 |
| Temperature and humidity | several points per floor, about four | our planning recommendation |
| Ceiling motion detectors | conservatively around 28 m² per detector | our planning, with overlap |
| Desk | one sensor per desk | our planning |
| Receivers | one per around 450 m², plus one per structurally separate area | our planning, deliberately conservative |
| Gateway | one per floor | our planning |
Model floor: devices, expansion stages and bill of materials →
Where the sensors go
InstallationThe location affects the reading more than the device does. Air sensors for CO2, temperature and humidity belong at 1.1 to 1.7 m on an interior wall, ideally opposite the door and around one metre away from door, window, supply air and heating surfaces. Motion detectors are mounted on the ceiling in the centre of the room, people counters above the passage at 2.2 to 2.5 m, desk sensors on or under the desktop.
What comes after commissioning
OperationEvery sensor sends a sign of life even when nothing changes; if it stops, the device appears on the alarm list. Batteries are replaced by condition, not by calendar. On our CO2 sensors, calibration is deliberately triggered via the service button – it is a maintenance service. Teach-in and commissioning are carried out by DEUTA Controls as a separate, chargeable service; afterwards the entire installation is contained in one configuration file.
Measuring occupancy without recording people
Data protectionOccupancy sensors detect motion, heat, distances or vibration – no images. What is transmitted are states such as “occupied” or count values, no data from which a person could be identified.
The processing must still be assessed under data protection law, by the party responsible for the building. Two things make this easier: evaluating occupancy per room or zone where the individual desk is not needed, and involving employee representatives early – in Germany, the works council generally has to be involved where technical equipment can be used to monitor behaviour or performance. We are happy to provide the technical description of the devices.
What sensors cost – and what it depends on
BudgetA reliable figure only comes with a floor plan and a task list. The items that determine the price can, however, be named in advance:
- Number of measuring points: it follows from task and expansion stage – ventilation needs far fewer devices than occupancy per desk.
- Power supply: devices on PoE or a power supply need cables and connections, solar and battery devices do not.
- Infrastructure: receivers per area, one gateway per floor, network connections.
- Commissioning: teach-in, assignment to rooms and data handover – a separate item.
- Operation: battery replacement by condition and CO2 calibration as a maintenance service.
What is not added: a licence fee per sensor. An expansion in stages makes sense – first ventilation, then occupancy, then the individual desk – just as on the model floor.
Checklist for designers
9 points- Define the tasks, then the measured variables: ventilation, room climate, occupancy, light, energy, protection.
- Mark the measuring locations on the floor plan: per meeting room, per zone, per desk.
- If a building standard applies, name it: WELL v2 Feature A08 or RESET Air – density and reporting interval differ.
- Specify the power supply per device group and include cabling for PoE and power supplies in the electrical design.
- Specify the wireless standard and device profile (EEP) for each item.
- Show receivers as a planning value, around 450 m² per receiver, and calculate separate areas separately.
- Define the data path to building automation – MQTT, BACnet, KNX or Modbus TCP – and who operates the broker.
- List commissioning, battery replacement and CO2 calibration as separate items.
- For occupancy measurement, involve data protection and employee representatives early.
Frequently asked questions
7 questionsWhich sensors does an office building need?
That depends on the tasks. For demand-controlled ventilation, CO2 sensors in the meeting rooms and temperature and humidity sensors in the open areas are enough. For space utilisation, motion detectors, people counters and desk sensors are added; for lighting on demand, motion and daylight; for energy monitoring, current sensors.
How many CO2 sensors does an office floor need?
One per meeting room, because each room is a measuring location of its own. In open areas, WELL v2 requires at least one monitor per 325 m², RESET Air one per space type and at most 500 m² per device.
What is a sensor gateway?
The device between wireless sensors and building automation. It collects the telegrams from the receivers, turns them into data points and passes them on via MQTT, BACnet, KNX or Modbus TCP. In our system this is the VL-700 BASE 2 for up to 500 sensors and 32 receivers.
Do wireless sensors need batteries?
Not all of them. Several of our sensors run on a solar cell and only have a battery as a backup; others run on battery, a power supply or PoE. For battery-only devices we expect a typical minimum service life of five years.
Can sensors be retrofitted in existing buildings?
Yes, and that is where wireless has the advantage: no cable runs to the sensors, only to the receivers on the ceiling. The existing building management system stays, the new values are added via an open interface. Whether existing EnOcean sensors can continue to be used depends on their device profile (EEP) – we will check that for you.
Is occupancy measurement compliant with data protection?
The sensors do not record images and only transmit states or count values. The assessment under data protection law lies with the party responsible for the building; for desks in Germany, the works council is involved. We provide the technical description.
What budget is realistic for building sensors?
A flat rate per square metre would not be serious. The price is determined by the number of measuring points, the power supply, receivers and gateways, and commissioning and maintenance; there are no licence fees per sensor. Send us your floor plan and tasks – you will receive a bill of materials with part numbers and a quote, in expansion stages if you wish.
Information as of 21 November 2026. Information on our devices from the product pages and the sensor overview; density guide values from WELL v2 (Feature A08, version Q4 2021), RESET Air (Commercial Interiors v2.0) and our planning practice. Information on data protection does not replace legal advice. The data sheets in their current version are authoritative.