VOC sensors: what they measure and when they make sense
A VOC sensor reacts to hundreds of volatile substances from paint, furniture, cleaning agents and breath – and yet outputs a single number. What that number means, how it is produced, why it is not a CO2 reading and in which rooms the measurement pays off.
What are VOCs?
Volatile organic compoundsVOC stands for volatile organic compounds: carbon-based substances that evaporate at room temperature and so enter the indoor air – solvents such as toluene or acetone, alcohols, aldehydes, fragrances such as limonene and many hundreds more.
The World Health Organization classifies them by boiling point: very volatile VVOCs, VOCs proper with boiling points between roughly 50 to 100 °C and 240 to 260 °C, and semi-volatile SVOCs. Strictly speaking, formaldehyde is a VVOC and is usually assessed separately in indoor hygiene.
Indoor VOC levels are often higher than outdoors because the sources are in the room itself. Part comes from people – breath and skin release acetone, isoprene and ethanol, among others – and a large part from building materials, furnishings and activities:
| Source | Typical substances | When it shows |
|---|---|---|
| New build and renovation | solvents from paints, varnishes, adhesives and floor coverings | in the first weeks and months after completion |
| Furniture and wood-based panels | formaldehyde, terpenes, aldehydes | after new furniture arrives, stronger when warm |
| Cleaning and disinfection | alcohols, fragrances such as limonene | during and shortly after cleaning |
| Printers and copiers | styrene and other substances, plus ultrafine particles | while printing, especially in small copy rooms |
| Kitchen and tea kitchen | substances from cooking and frying, plus particulate matter | at mealtimes |
| People | acetone, isoprene, ethanol from breath and skin | with occupancy, in parallel with CO2 |
How a metal-oxide sensor measures
The principleMost VOC sensors in room devices are metal-oxide sensors, MOX for short. They are small, inexpensive and respond sensitively to a wide range of substances. Four steps make up the measurement:
Four methods compared
From room sensor to laboratoryWhich method fits depends on the question: do you want to know whether the air is getting worse – or which substance is in the air and in what quantity? Only the laboratory fully answers the second question.
| Method | How it measures | Strength | Limit |
|---|---|---|---|
| Metal oxide (MOX) | a heated metal-oxide layer changes its resistance when organic substances react | small, inexpensive, sensitive, made for continuous measurement in the room | responds to many substances together, including hydrogen and carbon monoxide; delivers a total or an index, not individual substances |
| Photoionisation (PID) | a UV lamp ionises the molecules and the resulting current is measured | fast and very sensitive, common in portable devices for occupational safety and leak detection | considerably more expensive, the lamp ages; only detects substances whose ionisation energy is below the lamp energy – formaldehyde, for example, is not detected with the usual 10.6 eV lamp |
| Electrochemical | the gas reacts at an electrode; the current is a measure of the concentration | tailored to one substance, for example formaldehyde | measures only that one substance; cross-sensitivities, limited service life |
| Laboratory to ISO 16000-6 | air sample on a sorbent tube, analysed by gas chromatography and mass spectrometry | names individual substances with their concentration; basis of the TVOC value | snapshot, results only after days, no control possible |
A total, not a single substance: what the value means
Index and TVOCA MOX sensor cannot tell whether ethanol from a disinfectant or solvents from a new carpet are reacting on its layer. It sees the total – and each substance contributes with a different sensitivity. The individual shares cannot be calculated back from the one signal.
Manufacturers therefore either output an index or convert the signal into a TVOC value in µg/m³ or ppb using an assumed mixture of substances. Such a value is an estimate: if the mixture in the room differs from the assumption, so does the figure. Index scales are also manufacturer-specific and cannot be compared between devices from different manufacturers.
In practice this means: a VOC sensor is a very good trend and early-warning instrument. It shows when and how heavily the air is loaded and whether ventilation helps. Which substance is behind it can be clarified by a laboratory measurement if needed.
Assessing TVOC: the levels of the German Environment Agency
OrientationAccording to ISO 16000-6, TVOC (total volatile organic compounds) is the sum of the substances that appear between n-hexane and n-hexadecane in the laboratory analysis, calculated as toluene equivalent. For this total, the German Environment Agency (UBA) has published five levels for hygienic assessment:
| Level | TVOC | Hygienic assessment |
|---|---|---|
| 1 | up to 0.3 mg/m³ | harmless – target value |
| 2 | above 0.3 to 1 mg/m³ | still harmless, provided no guideline value for individual substances or substance groups is exceeded |
| 3 | above 1 to 3 mg/m³ | conspicuous |
| 4 | above 3 to 10 mg/m³ | of concern |
| 5 | above 10 mg/m³ | unacceptable |
VOC or CO2? Two questions, two measurands
The differenceCO2 shows how much exhaled air is in the room – in other words, whether ventilation matches the number of people. VOCs show what building materials, furnishings and activities release into the air, even when nobody is in the room. A freshly painted, empty room has normal CO2 and high VOCs; a full meeting room with low-emission furnishings has high CO2 and rather moderate VOCs.
Important when selecting a device: many inexpensive air quality sensors display an “eCO2” value. A MOX sensor calculates it from its VOC signal, assuming that VOCs and CO2 rise together with the number of people. That only holds as long as people are the only source. After mopping with a cleaning agent, such a sensor reports “high CO2” in an empty room – it does not see real CO2 at all. Ventilating to CO2 thresholds requires an NDIR sensor.
| CO2 | VOC | |
|---|---|---|
| Shows | exhaled air, air change per person | emissions from materials, activities and people |
| Method | NDIR or photoacoustic – measures the gas itself | mostly MOX – total of many substances |
| Reading | concentration in ppm | index or estimated total |
| Assessment | workplace rules, EN 16798-1 | UBA levels for TVOC from laboratory measurement |
| Controls | demand-controlled ventilation by occupancy | flushing after cleaning and construction, root-cause analysis |
When VOC measurement pays off – and when CO2 is enough
ApplicationIn most offices, classrooms and meeting rooms, CO2 is the right key indicator: people are the main load there, and CO2 captures them directly. VOCs are added where other sources play a role:
- New build and refurbishment: paints, adhesives and floor coverings outgas in the first months. The sensor shows when the values subside and whether flushing with outdoor air works.
- New furniture and fittings, especially wood-based panels and large surfaces in small rooms.
- Cleaning: the sensor shows how long cleaning agents and disinfectants linger and helps to coordinate cleaning times and ventilation.
- Print and copy rooms, tea kitchens and canteens: this is where VOCs and particulate matter come together.
- Workshops, laboratories and practices where solvents, adhesives or disinfectants are used – as a trend display, not as a substitute for mandatory workplace measurements.
- Complaints about odours or “bad air” despite good CO2 values.
CO2 alone is usually enough if low-emission materials have been installed (for example with Blue Angel or EMICODE EC1 labels), ventilation is designed for occupancy and there are no special sources in the room. Anyone seeking building certification should also check which measurands the standard requires.
Particulate matter and VOC in one device
EnoSense® PM VOCThe EnoSense® PM VOC measures the VOC index together with particulate matter in four fractions, temperature and humidity and transmits all values every four minutes via EnOcean radio. Particulate and VOC measurement need more energy than a solar cell and battery can supply; the device therefore runs on a 12 V plug-in power supply, which is included.
PM1.0, PM2.5, PM4 and PM10 denote particles up to a diameter of 1, 2.5, 4 and 10 micrometres; the EnoSense® PM VOC detects particles from 0.3 µm. The smaller the particles, the deeper they penetrate the airways. The 2021 WHO air quality guidelines, which apply to outdoor air, usually serve as orientation: PM2.5 annual mean 5 µg/m³, 24-hour mean 15 µg/m³.
| Measurand | Range | Accuracy according to data sheet |
|---|---|---|
| PM1.0 / PM2.5 | 0 to 1,000 µg/m³ | 0–100 µg/m³: ± 5 µg/m³ + 5 % of reading; 100–1,000 µg/m³: ± 10 % of reading |
| PM4 / PM10 | 0 to 1,000 µg/m³ | 0–100 µg/m³: ± 25 µg/m³; 100–1,000 µg/m³: ± 25 % of reading |
| VOC | index 1 to 500 | index-based assessment: 1 = very good, 500 = heavily polluted indoor air |
| Temperature | +10 to +40 °C | typ. ± 0.45 °C, max. ± 0.7 °C (at 15–30 °C, 50 % RH) |
| Humidity | 20 to 80 % RH | typ. ± 4.5 %, max. ± 6.0 % |
The built-in fan cleans itself about every seven days; no manual maintenance is required for this. It is specified at 24 dB(A) at a distance of 0.2 m. The device transmits using the manufacturer-specific profile EEP D1-09-08, as Part No. 12939 at 868.3 MHz for Europe and as Part No. 12967 at 902 MHz for the USA. An EnoDisc® receives the telegrams, and the VL-700 BASE 2 gateway passes the values on to the building automation system.
Where the sensor goes
LocationLike CO2, VOCs and particulate matter are measured in the occupied zone: on an interior wall, not in the supply air jet, not in the exhaust air and not right next to a source such as a printer or tea kitchen – otherwise the sensor measures the source instead of the room. The EnoSense® PM VOC data sheet gives a typical installation height of about 1.75 m. Because the device has a fan and its ventilation openings are on the underside, the area below it must be kept clear. Plan for a socket within reach.
Planning checklist
7 points- Clarify the question: trend and early warning in operation (sensor) or proof of individual substances (laboratory measurement to ISO 16000)?
- Ask for the measuring method: MOX, PID or single-gas sensor – and whether the device outputs an index or an estimated TVOC value.
- Do not use an “eCO2” value as CO2: plan an NDIR sensor for ventilation to CO2 thresholds.
- Select rooms by source: new build, new furniture, cleaning, printing, kitchen, workshop – not every office across the board.
- Consider particulate matter where printers, kitchens or outdoor air bring in particles.
- Plan the power supply: devices measuring VOCs and particulate matter usually need a power supply unit – provide a socket at the measuring location.
- Define thresholds and responses: at which value to ventilate, flush or look for the cause – and who receives the alert.
Frequently asked questions
7 questionsWhat does a VOC sensor measure?
The total of volatile organic compounds in the indoor air, such as solvents, alcohols and fragrances. It outputs an index or an estimated total for this, not individual substances.
How does a VOC sensor work?
Most use a heated metal-oxide layer (MOX). When organic substances react on its surface, its electrical resistance drops; the electronics convert this into an index. Portable instruments often use photoionisation (PID).
What is the difference between VOC and TVOC?
VOCs are the substances themselves. TVOC is their total, determined in the laboratory according to ISO 16000-6 and stated as toluene equivalent in mg/m³ or µg/m³. Sensors only estimate this total.
What TVOC level is good?
The German Environment Agency rates up to 0.3 mg/m³ as hygienically harmless (target value) and up to 1 mg/m³ as still harmless. Above 1 mg/m³ the air is considered conspicuous, above 3 mg/m³ of concern. The levels refer to laboratory measurements.
Can a VOC sensor measure CO2?
No. The “eCO2” value of some sensors is calculated from the VOC signal and can be high in an empty room after cleaning, for example. CO2 requires an NDIR sensor.
Do I need VOC in addition to CO2?
In normally used offices, CO2 is usually sufficient as the key indicator. VOC measurement pays off in new builds and refurbishments, with new furniture, intensive cleaning, in print and copy rooms, kitchens and workshops, and where there are odour complaints.
Are there presence detectors with a VOC sensor?
Combined devices exist, but VOCs are not suitable for detecting presence: the value rises with a delay and also without people, for example after cleaning. Presence is detected by motion and presence detectors; VOCs complement air quality.
Information as of 21 November 2026. General measurement technology and assessment according to the state of the art (ISO 16000-6, German Environment Agency, WHO air quality guidelines 2021); information on the EnoSense® PM VOC from its product page and data sheet (version of 20 November 2026). The data sheets in their current version are authoritative.