Know-how for lighting design · DALI

What is a DALI ballast (EVG)?

A DALI ballast is an electronic ballast – today usually an LED driver – with a digital DALI interface to IEC 62386. In German it is called a DALI-EVG. It powers the luminaire and receives switching and dimming commands over a two-wire line. This page explains what is inside, how it differs from a controller, a bus power supply and a gateway, and how to control DALI ballasts by radio or via Modbus TCP.

64short addresses per DALI line
16groups and 16 scenes per ballast
16 Vtypical bus voltage
2 mAmaximum per ballast from the bus
15ballasts on a BL-204 without extra supply

Ballast, LED driver, control gear

The term

EVG is the German abbreviation for elektronisches Vorschaltgerät, an electronic ballast (also ECG, electronic control gear). Originally it meant the device that starts and operates a fluorescent lamp. In LED luminaires the LED driver does this job. The DALI standard IEC 62386 covers both under the term control gear.

A DALI ballast has two sides: the mains connection, from which it draws the power for the light source, and two terminals for the DALI line. Over this line it receives commands – switch, dim, recall a scene – and answers queries, for example about its status or a lamp failure. It uses the bus only for communication, not to power the luminaire.

Which functions a ballast supports is described by its device type (DT). The general requirements for all control gear are in IEC 62386-102, the device-specific ones in separate parts:

Device typePart of the standardUsed for
DT0IEC 62386-201Ballasts for fluorescent lamps
DT6IEC 62386-207LED control gear, i.e. LED drivers with DALI
DT8IEC 62386-209Colour control, for example colour temperature (tunable white) or RGB

Every DALI ballast stores its own settings. This keeps an installation manageable after commissioning: the master sends short commands, and the ballast knows what to do.

  • Short address: one of 64 addresses per line (0 to 63).
  • Groups: membership in up to 16 groups.
  • Scenes: up to 16 stored light levels.
  • Limits and behaviour: minimum and maximum level, power-on level, level on bus failure and fade time.
  • Dimming curve: 254 steps, logarithmic – equal steps look even to the eye.

Four devices that are often confused

Roles on the line

Searches for a “DALI ballast”, a “DALI power supply” or a “DALI gateway” often mean different things. On a DALI line, each device has a clearly separate job.

Control gearBallast or LED driverSits in the luminaire, powers the light source from the mains and carries out the DALI commands. Up to 64 per line.
MasterControllerSends the commands: switches, dims, recalls scenes, assigns addresses during commissioning. Example: the BL-204-10-868 EVG FLEX EnOcean DALI controller.
SupplyBus power supplyProvides the bus voltage of typically 16 V so that communication is possible at all. Example: the AL-520-00 with up to 240 mA.
InterfaceGatewayMakes the DALI line accessible from another network. Example: the AL-511-00 IP-DALI-Bridge, DALI master and Modbus TCP converter in one.

What each device does

Compared

The table shows who does what on the line. One device can have several roles: the BL-204 is master and bus power supply, the AL-511-00 is master and gateway.

DevicePowers the luminaireSends commandsProvides bus voltageFrom DEUTA Controls
Ballast / LED driveryes, from the mainsno, only answers queriesno, draws up to 2 mAnot in our range – supplied by the luminaire manufacturer
Controller (master)noyesdepends on the deviceBL-204-10-868 EVG FLEX with 30 mA built in, BL-201 with 34 mA
Bus power supplynonoyesAL-520-00, up to 240 mA
Gatewaynoyes, on behalf of the higher-level systemdepends on the deviceAL-511-00 IP-DALI-Bridge, without its own supply
DEUTA Controls does not make ballasts or LED drivers. The DALI ballast is normally part of the luminaire; we supply what controls it: radio controllers, bus power supplies and gateways.

Bus voltage: when you need a bus power supply

In brief

Without bus voltage, no ballast can communicate. Under IEC 62386-101 it is typically 16 V and may range from 9.5 to 22.5 V. All power supplies on one line together may deliver no more than 250 mA; one ballast draws up to 2 mA.

Whether you need a separate bus power supply depends on the master. The BL-204-10-868 EVG FLEX has a 30 mA supply built in, enough for 15 ballasts. The AL-511-00 IP-DALI-Bridge has none; every line on it needs a bus power supply such as the AL-520-00 with up to 240 mA. An AL-520-00 in addition to a controller with a built-in supply would be too much: 270 mA is above the maximum of 250 mA.

Watch the wording: a “DALI power supply” for LED strips is a dimmable LED driver with a DALI input – a ballast on the line, not a bus power supply.

Bus current calculator: check the current budget of your line →

AL-520-00 bus power supply: when a line needs one →

Controlling DALI ballasts by radio

No control cable

Normally, push buttons and presence detectors need their own cable to the controller. With EnOcean, this cable is not needed: radio push buttons and sensors send their telegrams, mostly without a battery, to an EnOcean DALI controller. Acting as master, it converts them into DALI commands for the ballasts.

The BL-204-10-868 EVG FLEX is such a controller. It is supplied with 230 V AC, controls up to 15 DALI ballasts and provides their bus voltage with its built-in power supply (30 mA). At 148 x 21 x 19 mm it fits into the luminaire or a profile; metal housings are ruled out because the antenna is inside.

Configuration is wireless, using the free BL-PC-FLEX-2 software and an EnOcean USB stick: assign addresses, groups and scenes, set timers, link push buttons and sensors. With DT8 ballasts, the colour temperature can also be adjusted via push buttons. For flush mounting there is the BL-201 with 34 mA for up to 17 ballasts.

  1. Plan luminaires with DALI ballasts – up to 15 per BL-204.
  2. Connect the BL-204 to 230 V AC and to the DALI terminals of the ballasts.
  3. Address the ballasts with BL-PC-FLEX-2 and assign them to groups.
  4. Teach in radio push buttons, presence and light sensors and link them to groups or scenes.

View the BL-204-10-868 EVG FLEX →

Use case: lighting by presence and daylight →

Connecting DALI ballasts to Modbus TCP/IP

For building management

If a PLC or the building management system is to switch and dim the ballasts, a gateway sits between Ethernet and the DALI line. The AL-511-00 IP-DALI-Bridge is a DALI master with an Ethernet port and is addressed via Modbus TCP. It is supplied with 24 V DC and has no bus power supply of its own.

So each line has one bridge and one AL-520-00 bus power supply, for up to 64 ballasts. With several bridges, the installation can grow almost without limit over Ethernet.

Guide: EnOcean and DALI to Modbus TCP, KNX and MQTT →

View the AL-511-00 IP-DALI-Bridge →

Checklist: planning DALI ballasts correctly

7 points
  1. Check in the luminaire data sheet that the ballast has a DALI input to IEC 62386 – not just “dimmable” or 1–10 V.
  2. Choose the device type to suit the function: DT6 for LED, DT8 if colour temperature or colour is to be controlled.
  3. If DALI-2 is required, check the certification in the DALI Alliance product database.
  4. Split the lines: no more than 64 ballasts per line, with headroom for future luminaires.
  5. Draw up a current budget for each line: all power supplies together no more than 250 mA, consumption as per data sheet subtracted.
  6. Define the master: a radio controller such as the BL-204 (up to 15 ballasts, supply built in) or the AL-511-00 IP-DALI-Bridge with an AL-520-00 bus power supply.
  7. Define groups and scenes before addressing, and require the address plan at handover.

DALI for planners: cable length, cross-section, DALI-2 and D4i →

Frequently asked questions

7 questions

What does EVG mean in DALI?

EVG is the German abbreviation for elektronisches Vorschaltgerät, an electronic ballast. A DALI ballast operates the light source and also has a digital DALI interface to IEC 62386, through which it receives switching and dimming commands. In LED luminaires the device is usually called an LED driver; the standard calls both control gear.

Is a DALI ballast the same as a DALI LED driver?

In terms of the standard, yes: both are control gear on the DALI line. The term ballast dates from fluorescent lamps (device type DT0); LED drivers with DALI correspond to device type DT6, with colour control also DT8.

Does a DALI ballast need its own power supply?

Not for the light – the ballast is supplied directly from the mains. The DALI bus, however, needs a bus voltage of typically 16 V. It comes from the master if it has a built-in supply (BL-204: 30 mA), otherwise from a bus power supply such as the AL-520-00.

How many DALI ballasts fit on one line?

Up to 64 with their own short address, divided into up to 16 groups. How many actually work also depends on the current budget: with its built-in supply, the BL-204 powers up to 15 ballasts.

What do DT6 and DT8 mean?

They are DALI device types. DT6 (IEC 62386-207) stands for LED control gear, DT8 (IEC 62386-209) for colour control, such as tunable white. Which types a ballast supports is stated in its data sheet.

Can I control DALI ballasts by radio?

Yes, with an EnOcean DALI controller. The BL-204-10-868 EVG FLEX receives radio push buttons and sensors and, as DALI master, controls up to 15 ballasts – without an additional power supply and without a control cable to the push button.

How do I connect DALI ballasts to Modbus TCP?

With the AL-511-00 IP-DALI-Bridge. It is a DALI master with an Ethernet port and is addressed via Modbus TCP. Each line needs an AL-520-00 bus power supply; up to 64 ballasts per line are then possible.

Status and sources

Information as of 21 November 2026. Basics according to IEC 62386-101, -102, -201, -207 and -209; device values from the product pages and specification texts of the BL-204-10-868, AL-511-00 and AL-520-00. The wording of the standard and the data sheets of the devices in their current version are authoritative. DALI and DALI-2 are trademarks of the Digital Illumination Interface Alliance in various countries.

Controlling luminaires with DALI ballasts?

Send us your floor plan and luminaire list. You will receive a proposal for lines, controllers, bus power supplies and push buttons – with part numbers and a quote.