Know-how for planning · Overview

Building sensors: which sensors an office building needs

Which sensors an office building needs follows from the tasks, not from the catalogue. This guide leads from the task to the measured variable and the right sensor – with power supply, data path, sensor density and the questions to settle before the tender. The model floor shows what the finished plan looks like.

325 m²per CO2 monitor under WELL v2
12 mplanning radius per receiver
500sensors per gateway
1.1–1.7 mmounting height for air sensors
1gateway per floor

First the task, then the sensor

Six tasks

Nobody needs “sensors” as such. What is needed is ventilation that runs on demand, a room that can be booked when it is free, or evidence for occupational safety. If you write down the tasks first, the measured variables almost follow by themselves – and you avoid devices whose values nobody uses.

AirVentilate on demandCO2 shows how stale the air is. Particulate matter and VOC add to this where building standards or users ask for more.
ClimateControl heating and coolingTemperature, humidity and window status per room – so the control knows what is actually happening in the room.
OccupancyMake use of spacePresence, people count and occupied desks show which rooms are really used – for booking, cleaning and space planning.
LightLight on demandMotion and daylight ensure that lights are only on where someone is present and where it is too dark.
EnergyMake consumption visibleCurrent measurement per installation shows which loads run when – retrofittable with split-core current transformers.
ProtectionHealth and evidenceRadon on ground and basement floors, sound levels in open areas and evidence for WELL or RESET.

Which variable, which sensor

The overview

The table assigns each task its measured variable, the type of sensor and our matching device – with the power supply as listed in the sensor overview. Device names lead to the product page, the second link to the use case or article.

TaskMeasured variableSensor typeDevice and further readingPower supply
Ventilate on demandCO2, plus temperature and humidityNDIR CO2 sensor on the wall, display in the roomEnoSense® CO2
EnoPuck® CO2
Use case: Ventilate by CO2
EnoSense®: solar cell with backup battery · EnoPuck®: plug-in power supply 12 V DC
Air quality beyond CO2Particulate matter (PM1 to PM10), VOC indexParticle and VOC sensorEnoSense® PM VOC
Use case: Measure air quality
Plug-in power supply 12 V DC
Occupational safety on ground and basement floorsRadonRadon sensor with ionisation chamberEnoSense® RADON
Know-how: Radon in the workplace
PoE or 12 to 48 V DC
Control the room climateTemperature, relative humidityTemperature and humidity sensorEnoSense® Temp/RHBattery CR2032
Turn heating down while airingWindow open or closedMagnetic contact on the window frameEnoSense® WindowBattery CR2032
Light and rooms by presenceMotion, presencePIR motion detector on the ceilingEnoSense® PIR Ceiling
EnoSense® PIR DOT
Use case: Lighting by presence
PIR Ceiling: solar cell with backup battery · PIR DOT: battery CR3032
Use daylightIlluminance in luxLight sensorEnoSense® LUXBattery CR2032
Make use of rooms and areasPeople count, occupancy of an areaCounter above the door or ceiling sensor, no cameraEnoSense® People Counter
EnoSense® People Counter PRO
EnoSense® Presence Count
Know-how: People counting without a camera
People Counter: 2 × AA · PRO: PoE, USB or 12 to 48 V DC · Presence Count: PoE
Share desksOccupancy per deskMotion at the desk or vibration under the desktopEnoSense® Desk VIB
EnoSense® Desk
EnoSense® Wall+Desk
Use case: Desk occupancy
Desk, Desk VIB: battery CR2032 · Wall+Desk: solar cell with backup battery
Acoustics in open areasSound pressure levelSound sensorEnoSense® NOISE
EnoPuck® CO2 NOISE
EnoSense®: solar cell with 2 × AA · EnoPuck®: plug-in power supply 12 V DC
Energy per installationCurrent, three-phaseSplit-core current transformersEnoSense® 3PH Current Sense
Use case: Retrofit energy monitoring
Powered by its own current transformers
The table is the selection, the model floor is the result: there the same devices are installed on a fictitious office floor – with location, expansion stage and bill of materials.

Filter all sensors by part number and device profile →

View the model floor →

Solar, battery, power supply or PoE

Power supply

A sensor needs energy for measuring and transmitting. How much depends on the variable: a window contact reports rarely and needs little, a CO2 sensor runs a measuring cell, a radon sensor an ionisation chamber. This leads to different types of power supply – and each one ends up in a different trade.

Power supplyExamples from our rangeWhat it means for planning
Solar cell with backup batteryEnoSense® CO2, PIR Ceiling, Wall+Desk, NOISENo cable. Needs light at the mounting location; the battery bridges dark periods.
BatteryEnoSense® Temp/RH, LUX, Window, Desk, Desk VIB, PIR DOT, People CounterNo cable. Replace by condition, not by calendar; cell type and number belong in maintenance planning.
Plug-in power supplyEnoPuck® CO2, EnoPuck® CO2 NOISE, EnoSense® PM VOCPlan a socket at the mounting location.
PoEEnoSense® RADON, Presence Count, People Counter PRO, EnoDisc® receiversNetwork cable and PoE switch belong in electrical and IT planning.
From the measurementEnoSense® 3PH Current SensePowered by the current transformers that are clipped around the conductors anyway.

The power supply is specified per device group, not per wireless standard. How long batteries last and when they are replaced is covered in detail under operation and maintenance.

Operation and maintenance: battery, signs of life, calibration →

EnOcean for designers: where the energy comes from →

Wireless or wired?

Transmission

Wired sensors pay off where the cable is there anyway: in new buildings with a fixed room layout, or for devices that need mains power in any case. In existing buildings and on floors that change, wireless is usually the shorter route: no cable runs to the sensors, only to the receivers on the ceiling. This makes retrofitting possible during operation, and when the layout changes, the sensor simply moves along.

Our sensors transmit using EnOcean (ISO/IEC 14543-3-10), at 868.3 MHz in Europe. A telegram lasts about one millisecond – which is why a small solar cell is enough for many devices. The devices on PoE or a power supply also transmit their readings wirelessly; there the cable only provides power.

How EnOcean differs from Zigbee, LoRaWAN and Bluetooth LE, and when which standard fits, is covered in the comparison of wireless standards.

A comparison of wireless standards →

EnOcean for designers: range and receivers per floor →

From the sensor to building automation

Data path

A reading passes four stations. For planning, the last one matters most: which language does the system speak that takes over the values?

StationDeviceWhat happens
MeasureWireless sensorMeasures and transmits – on change and additionally as a sign of life.
ReceiveEnoDisc® on the ceiling, EnoDisc® 2 available soonPicks up the telegrams within a planning radius of around 12 m and passes them on via Ethernet.
EvaluateVL-700 BASE 2 gatewayCollects the values from up to 32 receivers and 500 sensors, evaluates them and keeps a history.
Hand overMQTT, BACnet, KNX, Modbus TCPPasses the values to building automation, dashboard or cloud – also via several routes in parallel.

Depending on the manufacturer, the gateway is also called a sensor gateway, IoT controller or edge controller; the individual wireless sensors are often called sensor nodes. The gateway is where wireless telegrams become data points. If you run your own platform, you can also connect the EnoDisc® 2 directly to your own MQTT broker.

Which data path fits: MQTT, BACnet, KNX and Modbus TCP →

EnOcean and DALI to Modbus TCP, KNX and MQTT →

VL-700 BASE 2 gateway →

EnoDisc® 2 receiver →

How many sensors does a floor need?

Sensor density

The number of sensors follows from the measuring locations, not from the floor area alone. A meeting room is a measuring location of its own, however small; an open area is divided into zones. These guide values come from building standards and from our planning:

WhatGuide valueSource
CO2 in open areasat least one monitor per 325 m²WELL v2, Feature A08
CO2 under RESET Airone device per space type, at most 500 m² per deviceRESET Air, Commercial Interiors
CO2 in meeting roomsone sensor per roomseparate measuring location, our planning
Display in the roomone per 325 m²WELL v2, Feature A08
Temperature and humidityseveral points per floor, about fourour planning recommendation
Ceiling motion detectorsconservatively around 28 m² per detectorour planning, with overlap
Deskone sensor per deskour planning
Receiversone per around 450 m², plus one per structurally separate areaour planning, deliberately conservative
Gatewayone per floorour planning
Worked example: the model floor equips a fictitious 900 m² office floor with 15 meeting rooms and 50 desks – with 26 devices in the basic stage, 54 with occupancy, and 121 in full expansion. Five receivers and one gateway complete it.

Model floor: devices, expansion stages and bill of materials →

WELL and RESET: the proof, line by line →

Where the sensors go

Installation

The location affects the reading more than the device does. Air sensors for CO2, temperature and humidity belong at 1.1 to 1.7 m on an interior wall, ideally opposite the door and around one metre away from door, window, supply air and heating surfaces. Motion detectors are mounted on the ceiling in the centre of the room, people counters above the passage at 2.2 to 2.5 m, desk sensors on or under the desktop.

Installation height and location per device →

What comes after commissioning

Operation

Every sensor sends a sign of life even when nothing changes; if it stops, the device appears on the alarm list. Batteries are replaced by condition, not by calendar. On our CO2 sensors, calibration is deliberately triggered via the service button – it is a maintenance service. Teach-in and commissioning are carried out by DEUTA Controls as a separate, chargeable service; afterwards the entire installation is contained in one configuration file.

Operation and maintenance →

Measuring occupancy without recording people

Data protection

Occupancy sensors detect motion, heat, distances or vibration – no images. What is transmitted are states such as “occupied” or count values, no data from which a person could be identified.

The processing must still be assessed under data protection law, by the party responsible for the building. Two things make this easier: evaluating occupancy per room or zone where the individual desk is not needed, and involving employee representatives early – in Germany, the works council generally has to be involved where technical equipment can be used to monitor behaviour or performance. We are happy to provide the technical description of the devices.

People counting without a camera →

What sensors cost – and what it depends on

Budget

A reliable figure only comes with a floor plan and a task list. The items that determine the price can, however, be named in advance:

  • Number of measuring points: it follows from task and expansion stage – ventilation needs far fewer devices than occupancy per desk.
  • Power supply: devices on PoE or a power supply need cables and connections, solar and battery devices do not.
  • Infrastructure: receivers per area, one gateway per floor, network connections.
  • Commissioning: teach-in, assignment to rooms and data handover – a separate item.
  • Operation: battery replacement by condition and CO2 calibration as a maintenance service.

What is not added: a licence fee per sensor. An expansion in stages makes sense – first ventilation, then occupancy, then the individual desk – just as on the model floor.

Request a quote for your building →

Checklist for designers

9 points
  1. Define the tasks, then the measured variables: ventilation, room climate, occupancy, light, energy, protection.
  2. Mark the measuring locations on the floor plan: per meeting room, per zone, per desk.
  3. If a building standard applies, name it: WELL v2 Feature A08 or RESET Air – density and reporting interval differ.
  4. Specify the power supply per device group and include cabling for PoE and power supplies in the electrical design.
  5. Specify the wireless standard and device profile (EEP) for each item.
  6. Show receivers as a planning value, around 450 m² per receiver, and calculate separate areas separately.
  7. Define the data path to building automation – MQTT, BACnet, KNX or Modbus TCP – and who operates the broker.
  8. List commissioning, battery replacement and CO2 calibration as separate items.
  9. For occupancy measurement, involve data protection and employee representatives early.

Frequently asked questions

7 questions

Which sensors does an office building need?

That depends on the tasks. For demand-controlled ventilation, CO2 sensors in the meeting rooms and temperature and humidity sensors in the open areas are enough. For space utilisation, motion detectors, people counters and desk sensors are added; for lighting on demand, motion and daylight; for energy monitoring, current sensors.

How many CO2 sensors does an office floor need?

One per meeting room, because each room is a measuring location of its own. In open areas, WELL v2 requires at least one monitor per 325 m², RESET Air one per space type and at most 500 m² per device.

What is a sensor gateway?

The device between wireless sensors and building automation. It collects the telegrams from the receivers, turns them into data points and passes them on via MQTT, BACnet, KNX or Modbus TCP. In our system this is the VL-700 BASE 2 for up to 500 sensors and 32 receivers.

Do wireless sensors need batteries?

Not all of them. Several of our sensors run on a solar cell and only have a battery as a backup; others run on battery, a power supply or PoE. For battery-only devices we expect a typical minimum service life of five years.

Can sensors be retrofitted in existing buildings?

Yes, and that is where wireless has the advantage: no cable runs to the sensors, only to the receivers on the ceiling. The existing building management system stays, the new values are added via an open interface. Whether existing EnOcean sensors can continue to be used depends on their device profile (EEP) – we will check that for you.

Is occupancy measurement compliant with data protection?

The sensors do not record images and only transmit states or count values. The assessment under data protection law lies with the party responsible for the building; for desks in Germany, the works council is involved. We provide the technical description.

What budget is realistic for building sensors?

A flat rate per square metre would not be serious. The price is determined by the number of measuring points, the power supply, receivers and gateways, and commissioning and maintenance; there are no licence fees per sensor. Send us your floor plan and tasks – you will receive a bill of materials with part numbers and a quote, in expansion stages if you wish.

Status and sources

Information as of 21 November 2026. Information on our devices from the product pages and the sensor overview; density guide values from WELL v2 (Feature A08, version Q4 2021), RESET Air (Commercial Interiors v2.0) and our planning practice. Information on data protection does not replace legal advice. The data sheets in their current version are authoritative.