The VL-700 BASE receives the radio telegrams of up to 500 EnOcean sensors, decodes the device profiles and publishes every reading as JSON to your MQTT broker – ready to read, with no EEP knowledge needed on the receiving side.
How a reading gets to the broker
Four stepsWhat is on the topic
JSON per telegramOne JSON object per radio telegram. If a device measures several values, they appear together in the “functions” list.
{
"eepId": "47D10901",
"deviceId": "0421A3F7",
"friendlyId": "Room-201-CO2",
"timestamp": 1790935200000,
"dbm": -71,
"functions": [
{ "key": "CO2", "range": "0 to 5.000 ppm", "value": 612 },
{ "key": "Humidity", "range": "0 to 100 %", "value": 44 },
{ "key": "Temperature", "range": "+10 to +35 °C", "value": 22.4 }
],
"telegramInfo": { "dbm": -71 },
"topic": "deuta/floor2"
}Structure as sent by the device; device ID, name and values are example values.
| Field | Content |
|---|---|
| eepId | Device profile of the sensor (EnOcean Equipment Profile) |
| deviceId | EnOcean ID of the sensor, eight hexadecimal digits |
| friendlyId | the plain name assigned during set-up |
| timestamp | Time of reception as Unix time in milliseconds |
| dbm | Received signal strength in dBm |
| functions | List of readings: name (key), measuring range with unit (range), value (value) |
| topic | the topic the message was published on |
| Topic form | Structure | When it makes sense |
|---|---|---|
| Static | one fixed topic for all devices of the gateway | the standard case: one subscription is enough, devices are distinguished in the payload |
| Dynamic | <prefix>/<device profile>/<device ID> | when the target system should filter by topic |
| Custom | exactly the agreed string | when an existing topic structure at the customer has to be respected |
A gateway instead of a USB stick
The comparisonFor one room, a USB stick with an open-source script is enough. For a building, what counts is who takes care of radio coverage, device profiles and operation.
| USB stick + script | VL-700 BASE | |
|---|---|---|
| Reception | one receiver on the computer | up to 32 EnoDisc® across the building, via PoE |
| Device profiles | assign and maintain yourself | decoded in the gateway, readings with units |
| EnOcean Secure | the computer has to handle decryption | decrypted in the gateway (AES-128, rolling code, CMAC) |
| Outputs | MQTT | MQTT to up to 4 brokers, plus BACnet, Modbus TCP, KNX, OPC UA in parallel |
| Operation | own script, own computer | DIN-rail device operated in the browser, remote support available |
| Cost per sensor | none | none |
Where the values go
After the brokerAnything that understands MQTT and JSON can take over the values – for example Node-RED for your own flows, Home Assistant via its MQTT integration, InfluxDB with Grafana for history, or your own software. In parallel, the same gateway can serve the building automation via BACnet, Modbus TCP or KNX.
Frequently asked questions
7 questionsDo I need EEP knowledge?
No. The VL-700 BASE decodes the device profiles itself; the JSON contains readings with names and units.
Which broker can I use?
Your own, for example Mosquitto on premises, or a broker in the cloud. The connection can run via TLS.
Can the gateway send to several brokers at the same time?
Yes, to up to four MQTT brokers in parallel – for example to the on-site building automation and to an analytics platform.
Is the radio data encrypted?
With EnOcean Secure, yes: the VL-700 BASE decrypts AES-128-encrypted telegrams itself before passing them on as JSON. Encrypted and unencrypted sensors can be mixed.
Which sensors are supported?
Our own EnoSense sensors and EnOcean devices from other manufacturers with the common device profiles for room sensors. We check in advance which profiles your project needs.
Is there a REST interface?
Not today; it is in preparation. Today, the values go out via MQTT, BACnet, KNX or Modbus TCP.
Are there licence fees?
No. There is no fee per sensor and no recurring cost.
Information as of 2 October 2026. The VL-700 BASE manual in its current version is authoritative for the field structure.
Planning EnOcean over MQTT?
Send us your floor plan, sensor list and target system – you will receive a device list with order numbers and a quote.