What is a DALI ballast (EVG)?
A DALI ballast is an electronic ballast – today usually an LED driver – with a digital DALI interface to IEC 62386. In German it is called a DALI-EVG. It powers the luminaire and receives switching and dimming commands over a two-wire line. This page explains what is inside, how it differs from a controller, a bus power supply and a gateway, and how to control DALI ballasts by radio or via Modbus TCP.
Ballast, LED driver, control gear
The termEVG is the German abbreviation for elektronisches Vorschaltgerät, an electronic ballast (also ECG, electronic control gear). Originally it meant the device that starts and operates a fluorescent lamp. In LED luminaires the LED driver does this job. The DALI standard IEC 62386 covers both under the term control gear.
A DALI ballast has two sides: the mains connection, from which it draws the power for the light source, and two terminals for the DALI line. Over this line it receives commands – switch, dim, recall a scene – and answers queries, for example about its status or a lamp failure. It uses the bus only for communication, not to power the luminaire.
Which functions a ballast supports is described by its device type (DT). The general requirements for all control gear are in IEC 62386-102, the device-specific ones in separate parts:
| Device type | Part of the standard | Used for |
|---|---|---|
| DT0 | IEC 62386-201 | Ballasts for fluorescent lamps |
| DT6 | IEC 62386-207 | LED control gear, i.e. LED drivers with DALI |
| DT8 | IEC 62386-209 | Colour control, for example colour temperature (tunable white) or RGB |
Every DALI ballast stores its own settings. This keeps an installation manageable after commissioning: the master sends short commands, and the ballast knows what to do.
- Short address: one of 64 addresses per line (0 to 63).
- Groups: membership in up to 16 groups.
- Scenes: up to 16 stored light levels.
- Limits and behaviour: minimum and maximum level, power-on level, level on bus failure and fade time.
- Dimming curve: 254 steps, logarithmic – equal steps look even to the eye.
Four devices that are often confused
Roles on the lineSearches for a “DALI ballast”, a “DALI power supply” or a “DALI gateway” often mean different things. On a DALI line, each device has a clearly separate job.
What each device does
ComparedThe table shows who does what on the line. One device can have several roles: the BL-204 is master and bus power supply, the AL-511-00 is master and gateway.
| Device | Powers the luminaire | Sends commands | Provides bus voltage | From DEUTA Controls |
|---|---|---|---|---|
| Ballast / LED driver | yes, from the mains | no, only answers queries | no, draws up to 2 mA | not in our range – supplied by the luminaire manufacturer |
| Controller (master) | no | yes | depends on the device | BL-204-10-868 EVG FLEX with 30 mA built in, BL-201 with 34 mA |
| Bus power supply | no | no | yes | AL-520-00, up to 240 mA |
| Gateway | no | yes, on behalf of the higher-level system | depends on the device | AL-511-00 IP-DALI-Bridge, without its own supply |
Bus voltage: when you need a bus power supply
In briefWithout bus voltage, no ballast can communicate. Under IEC 62386-101 it is typically 16 V and may range from 9.5 to 22.5 V. All power supplies on one line together may deliver no more than 250 mA; one ballast draws up to 2 mA.
Whether you need a separate bus power supply depends on the master. The BL-204-10-868 EVG FLEX has a 30 mA supply built in, enough for 15 ballasts. The AL-511-00 IP-DALI-Bridge has none; every line on it needs a bus power supply such as the AL-520-00 with up to 240 mA. An AL-520-00 in addition to a controller with a built-in supply would be too much: 270 mA is above the maximum of 250 mA.
Bus current calculator: check the current budget of your line →
Controlling DALI ballasts by radio
No control cableNormally, push buttons and presence detectors need their own cable to the controller. With EnOcean, this cable is not needed: radio push buttons and sensors send their telegrams, mostly without a battery, to an EnOcean DALI controller. Acting as master, it converts them into DALI commands for the ballasts.
The BL-204-10-868 EVG FLEX is such a controller. It is supplied with 230 V AC, controls up to 15 DALI ballasts and provides their bus voltage with its built-in power supply (30 mA). At 148 x 21 x 19 mm it fits into the luminaire or a profile; metal housings are ruled out because the antenna is inside.
Configuration is wireless, using the free BL-PC-FLEX-2 software and an EnOcean USB stick: assign addresses, groups and scenes, set timers, link push buttons and sensors. With DT8 ballasts, the colour temperature can also be adjusted via push buttons. For flush mounting there is the BL-201 with 34 mA for up to 17 ballasts.
- Plan luminaires with DALI ballasts – up to 15 per BL-204.
- Connect the BL-204 to 230 V AC and to the DALI terminals of the ballasts.
- Address the ballasts with BL-PC-FLEX-2 and assign them to groups.
- Teach in radio push buttons, presence and light sensors and link them to groups or scenes.
Connecting DALI ballasts to Modbus TCP/IP
For building managementIf a PLC or the building management system is to switch and dim the ballasts, a gateway sits between Ethernet and the DALI line. The AL-511-00 IP-DALI-Bridge is a DALI master with an Ethernet port and is addressed via Modbus TCP. It is supplied with 24 V DC and has no bus power supply of its own.
So each line has one bridge and one AL-520-00 bus power supply, for up to 64 ballasts. With several bridges, the installation can grow almost without limit over Ethernet.
Checklist: planning DALI ballasts correctly
7 points- Check in the luminaire data sheet that the ballast has a DALI input to IEC 62386 – not just “dimmable” or 1–10 V.
- Choose the device type to suit the function: DT6 for LED, DT8 if colour temperature or colour is to be controlled.
- If DALI-2 is required, check the certification in the DALI Alliance product database.
- Split the lines: no more than 64 ballasts per line, with headroom for future luminaires.
- Draw up a current budget for each line: all power supplies together no more than 250 mA, consumption as per data sheet subtracted.
- Define the master: a radio controller such as the BL-204 (up to 15 ballasts, supply built in) or the AL-511-00 IP-DALI-Bridge with an AL-520-00 bus power supply.
- Define groups and scenes before addressing, and require the address plan at handover.
DALI for planners: cable length, cross-section, DALI-2 and D4i →
Frequently asked questions
7 questionsWhat does EVG mean in DALI?
EVG is the German abbreviation for elektronisches Vorschaltgerät, an electronic ballast. A DALI ballast operates the light source and also has a digital DALI interface to IEC 62386, through which it receives switching and dimming commands. In LED luminaires the device is usually called an LED driver; the standard calls both control gear.
Is a DALI ballast the same as a DALI LED driver?
In terms of the standard, yes: both are control gear on the DALI line. The term ballast dates from fluorescent lamps (device type DT0); LED drivers with DALI correspond to device type DT6, with colour control also DT8.
Does a DALI ballast need its own power supply?
Not for the light – the ballast is supplied directly from the mains. The DALI bus, however, needs a bus voltage of typically 16 V. It comes from the master if it has a built-in supply (BL-204: 30 mA), otherwise from a bus power supply such as the AL-520-00.
How many DALI ballasts fit on one line?
Up to 64 with their own short address, divided into up to 16 groups. How many actually work also depends on the current budget: with its built-in supply, the BL-204 powers up to 15 ballasts.
What do DT6 and DT8 mean?
They are DALI device types. DT6 (IEC 62386-207) stands for LED control gear, DT8 (IEC 62386-209) for colour control, such as tunable white. Which types a ballast supports is stated in its data sheet.
Can I control DALI ballasts by radio?
Yes, with an EnOcean DALI controller. The BL-204-10-868 EVG FLEX receives radio push buttons and sensors and, as DALI master, controls up to 15 ballasts – without an additional power supply and without a control cable to the push button.
How do I connect DALI ballasts to Modbus TCP?
With the AL-511-00 IP-DALI-Bridge. It is a DALI master with an Ethernet port and is addressed via Modbus TCP. Each line needs an AL-520-00 bus power supply; up to 64 ballasts per line are then possible.
Information as of 21 November 2026. Basics according to IEC 62386-101, -102, -201, -207 and -209; device values from the product pages and specification texts of the BL-204-10-868, AL-511-00 and AL-520-00. The wording of the standard and the data sheets of the devices in their current version are authoritative. DALI and DALI-2 are trademarks of the Digital Illumination Interface Alliance in various countries.
Controlling luminaires with DALI ballasts?
Send us your floor plan and luminaire list. You will receive a proposal for lines, controllers, bus power supplies and push buttons – with part numbers and a quote.