Planning Information

Mounting Height and Location

How high should a sensor be installed? In short: Air sensors for CO2, temperature, and humidity should be installed at a height of 1.1 to 1.7 m; motion detectors should be mounted on the ceiling at 2.5 m; people counters should be placed above the passageway at 2.2 to 2.5 m; and table sensors should be mounted on or under the tabletop. Detailed information, broken down by device and including explanations, can be found here.

1.1–1.7 mAir sensors in the breathing zone
2.5 mMotion detectors on the ceiling
2.2–2.5 mPeople counter above the passageway
4 mPresence count for 7 × 3 m

At what height should a CO2 sensor be installed?

The most common question

A CO₂ sensor is installed 1.1 to 1.7 meters above the finished floor. This is the breathing zone of people who are sitting or standing, and it is precisely this air that should be measured—not the air at floor level or the air near the ceiling. Our data sheet specifies an installation height of approximately 1.75 m; where WELL certification is sought, 1.1 to 1.7 m is explicitly required. To meet both requirements, install the sensor at 1.7 m.

More important than the exact centimeter is the sensor’s location in the room. The sensor should be mounted on an interior wall, preferably opposite the door. If placed next to the door, it measures the hallway; if placed in the supply air stream, it measures the HVAC system; and if placed in the exhaust air stream, it measures a mixed value that has little to do with the room itself. As a rule of thumb, we allow for a one-meter distance from doors, windows, supply air, exhaust air, and heating and cooling surfaces.

Where certification is required, the range is specified in the guidelines: WELL v2 requires 1.1 to 1.7 m for measuring devices and displays, while RESET Air permits 0.9 to 1.8 m and additionally requires a minimum distance of 5 m from openable windows and supply air vents. Without certification, the breathing zone is considered the standard, i.e., 1.2 to 1.8 m.

The same applies to temperature and humidity: measurements are taken where people are present. A sensor on the exterior wall measures the wall temperature, and one above the radiator measures the heating. Four measurement points per floor show whether the area is being heated evenly.

The height is a range, not a specific point. The CO2 level changes very little between 1.1 and 1.7 m. Whether the sensor is mounted next to the door or across from it makes a big difference. If you can only include one piece of information in the request for proposals, specify the location.

Ceiling, Wall, Work Surface: The Three Levels

All devices in a table

A fully equipped floor has devices on three levels. Items that need to monitor an area are mounted on the ceiling: motion detectors, meters, and wireless receivers. Items that measure air quality or display information are mounted on the wall. Items specific to individual workstations are located at the work surface.

The following table lists the installation location, height, and reason for each device. The values are taken from the product data sheets, the model floor, and—where required by certification—from WELL.

DeviceInstallation locationHeightWhat to Keep in Mind
EnoSense® CO2, EnoPuck® CO2Inner wall opposite the door1.1 to 1.7 mNot next to the door, not in the supply air stream, not in the exhaust air—otherwise, the device will measure the hallway instead of the room. Our data sheet recommends approximately 1.75 m; where WELL standards apply, 1.1 to 1.7 m is required.
EnoSense® Temp/RHIn common areas, multiple points per floor1.1 to 1.7 mAt least 1 m away from exterior walls, doors, direct sunlight, supply and exhaust air, and heating and cooling surfaces. Four measurement points per floor indicate whether the area is being evenly heated or cooled.
EnoSense® PM VOCWall mounting with included bracketOccupancy areaParticles and VOCs are measured in the breathing zone, just like CO2. Do not place the sensor in the supply air or directly next to a source such as a printer or break room.
EnoSense® RadonIn the room to be assessedLiving areaThe measurement location should be within the room for which the certification applies—that is, in the workspace itself, not in the hallway outside it. Check the operating temperature of the installation site; the minimum temperature is +10 °C.
EnoSense® PIR Ceiling, PIR DOTCeiling, center of the room2.5 mAt a mounting height of 2.5 m, the detection radius is approximately 3 m. When mounted higher, the detection area increases, but sensitivity at the edges decreases.
EnoSense® Presence CountCeiling above the area to be counted4 mAt a mounting height of 4 m, an area of up to 7 × 3 m is detected. Mount using the holes in the base plate, with the sensors facing forward.
EnoSense® People CounterCeiling, above the passageway2.2 to 2.5 m, typically 2.4 mCounts people passing through without detecting individual locations. Detection range is approximately 0.5 m in front of and 0.2 m behind the sensor.
EnoSense® DeskOn the tabletoptypically 0.85 mDetection angle approximately 90 degrees; detection range about 0.5 m in front of the sensor. Oriented toward the workstation, not toward the aisle.
EnoSense® Desk VIBUnder the tabletopTable heightOne sensor per workstation. Installation is possible even while the office is in operation, without requiring any configuration.
EnoSense® LUXFor windowsWork surfaceMeasures natural light to ensure the lighting system only provides as much light as necessary. Avoid placing it in the shadow of a shelf or directly under a light fixture.
EnoSense® WindowOn a window that opensWindow frameReports the window status to the control system so that the heating system does not work against the open window when ventilating.
EnoSign® Room DisplayWall-mounted, visible at the entrance1.1 to 1.7 mWELL requires displays to be installed at the same height as measuring devices, with one display per 325 m². The EnoSign displays the readings from any sensor without taking measurements itself and without requiring wiring.
EnoDisc® Wireless ReceiverCeiling, offset from the centerlineCeiling heightWith a planning radius of 12 m, one receiver covers approximately 450 m²; the coverage areas intentionally overlap. Connection via RJ45 or LSA, powered via PoE.
VL-700 BASE GatewayUtility Room, DIN RailControl cabinetOne gateway per floor, with a firewall between the field network and the building network. From here, the data is sent to the building automation system.
"Ceiling" does not mean "structural ceiling." For suspended ceilings, the lower edge is considered the installation height. If the specifications list the structural ceiling height, the detector will ultimately be mounted 30 cm too high and will cover a larger area with reduced sensitivity at the edges.

Where a device must not be hung

Five Mistakes That Stand Out During Operation

Most complaints about “incorrect readings” are due to installation errors. Five of these errors occur time and again, and all five are cheaper to prevent during installation than to explain during the acceptance inspection.

In the supply air stream: the sensor measures the system, not the room, and the control system works against itself. Next to the door: every time the door opens, the hallway temperature is drawn in, causing the reading to fluctuate erratically. In direct sunlight or above a radiator: the temperature reading becomes inaccurate, and in combined units, the humidity level drops as well.

Behind a shelf or a plant: the air doesn’t circulate, and the reading lags behind. And if the motion detector is in the corner of the room instead of in the center: half of its detection cone points toward the wall, leaving half the room uncovered. At a mounting height of 2.5 m, a ceiling-mounted detector covers a radius of about 3 m—which only works if it’s centered.

Before the Call for ProposalsDetermine the location for each roomMark on the floor plan which wall the unit will be mounted on. The phrase “Install according to manufacturer’s instructions” defers the decision to the construction site, where proximity will be the deciding factor.
On the construction siteCheck the substrateDrywall, concrete, and glass partitions require different mounting methods. For glass and metal, the radio line of sight must also be checked.
After installationDocument the locationThe room number, device ID, and installation location should all be included in the same list. Without this information, it will be unclear which device is being referred to when the batteries are first replaced.

What this means for your request for proposals

9 points
  • Specify the mounting height for each group of devices; do not rely on “manufacturer specifications.”
  • Where WELL applies: Specify 1.1 to 1.7 m for air sensors and displays.
  • Specify the installation location for each room: interior wall opposite the door, ceiling in the center of the room, above the doorway.
  • Specify minimum clearances: one meter from doors, windows, supply air vents, exhaust air vents, and heating and cooling surfaces.
  • For suspended ceilings, specify the lower edge as the reference point, not the exposed ceiling.
  • For meters, check the clearance height: 2.2 to 2.5 m, typically 2.4 m.
  • Specify fasteners and substrate for each room type.
  • Determine who will install the devices: users can install table sensors themselves; ceiling-mounted devices are the responsibility of the electrical contractor.
  • Require the following information for measurements and documentation: room number, device ID, and installation location.
Status and Sources

Information current as of September 16, 2026. Regulatory information has been compiled to the best of our knowledge and does not constitute legal advice. The text of the currently applicable version is always authoritative.

  • Installation heights and locations for each device are specified in the respective product data sheets (under “Installation Height”), as of September 2026.
  • WELL v2, Feature A08 “Air Quality Monitoring and Awareness,” Q4 2021 version: Installation height 1.1 to 1.7 m for measuring devices and displays.
  • RESET™ Air Standard for Commercial Interiors v2.0 dated January 31, 2018, Section 2.2.6: Installation height 0.9 to 1.8 m, minimum distance of 5 m from openable windows and supply air vents.
  • Placement and rationale for each device from the sample floor plan on this website (121 devices, three configuration levels).
  • A minimum distance of one meter from doors, windows, supply air vents, exhaust air vents, and heating surfaces is our design recommendation—not a requirement set forth by a standard.