Tender Text · Order No. 12432, 12452, 12465, 12466, 12467, 12468, 12760, 12604, 12759, 12518, 12537, 12791, 12538

Specification Text for EnoSense® People Counter

The complete specification item in plain text, ready to be copied into your bill of quantities—including the technical details that belong to the item. As a Word file with quantity and price columns alongside.

Text to copy

Item 1.1.1

EnoSense People Counter, black, 868 MHz, CE-
, battery-powered EnOcean sensor for people counting with an integrated wireless interface.

Application/TypePeople-counting sensor
Power Supply2 AA batteries, factory-installed
InterfaceEnOcean (868 MHz)
HousingPC V0, Color: RAL 9004, Signal Black, Protection Class: IP20 in accordance with DIN EN 60529
InstallationInstall flat on the surface / door frame; attach using the included pre-assembled pad
Dimensions36 x 37 x 80 mm
BrandDEUTA Controls GmbH
Item NumberAL-436-00-868
Order Numbers12432, 12452, 12465, 12466, 12467, 12468, 12760, 12604, 12759, 12518, 12537, 12791, 12538

How to include this item: The text is worded so that it can be inserted into a bill of quantities without any changes. The Word file includes the item number, quantity, and price columns.

The radio frequency depends on the country where the system will be operated, not on the purchaser’s location. Before awarding the contract, verify that the order number is appropriate for your market’s regulatory requirements.

All tender documents →

Specifications for the item

From the data sheet

These values should be included in the specifications if you want to specify the device precisely—or left intentionally open to allow for alternatives.

Wireless InterfaceEnOcean
EU: 868.3 MHz
FCC: 902 MHz
ARIB: 928 MHz
Additional InterfacesService button
SensorsPIR for people counting, no camera
Power Supply2x AA, VARTA Industrial, included
Environmental ConditionsOperating temperature: +5 °C to +40 °C
Storage temperature: -20 °C to +70 °C
Humidity: 0 to 95%
Protection class: IP20
Dimensions and Weight36 x 37 x 80 mm
94 g
Installation locationCeiling, above the passageway
Installation height2.2 to 2.5 m, typically 2.4 m
Device Profile (EEP)D1-07-10
ApprovalsEuropean Union (CE), North America (FCC), Japan (ARIB), Taiwan (NCC), South Korea (KC), Singapore (IMDA), China (CCC)
Range, System Limits, and Mounting Heights →

Is this device suitable for your project?