Radon in the Workplace
Radon is a naturally occurring radioactive noble gas that seeps into buildings from the ground. For workplaces, the Radiation Protection Act specifies a reference value and requires measurements in certain cases. Here’s what that means for your planning.
What the Law Requires
Radiation Protection ActThe Radiation Protection Act specifies a reference value of 300 becquerels per cubic meter for common areas and workplaces, averaged over a calendar year. This is expressly not a limit value: if it is exceeded, measures must be evaluated and implemented. If the concentration remains above this level thereafter, the workplace must be reported to the competent authority, and the employees’ exposure must be assessed.
There is no mandatory testing requirement everywhere. It applies to workplaces in basements and on the ground floor in areas designated by a federal state as radon-prone areas, as well as to certain workplaces—regardless of the area—such as water treatment plants, underground facilities, exhibition mines, and radon spas. Measurements must be taken within 18 months of the start of operations or after the area has been designated.
For planning purposes, this means two things: First, the building’s location determines whether measurements are required at all. Second, the floor level determines which rooms are affected. Both factors must be considered before selecting the equipment, not after.
Annual measurement is not monitoring
Two different questionsThe measurement required by law uses passive nuclear track detectors, which are hung in the room for twelve months and then analyzed by an accredited laboratory. The result is a single number: the annual average. It answers the question of whether action is required.
It does not answer the question of whether a measure is effective. Radon concentrations fluctuate significantly over the course of the day and year: they are higher at night and during the heating season, and significantly lower when ventilation is running. An annual average of 280 Bq/m³ can result from quiet days and a few nights with very high levels.
Continuous monitoring shows this trend. It reveals when the values rise, whether a change in ventilation strategy is having an effect, and whether a structural measure has achieved its intended result. The two methods are not interchangeable: the annual measurement fulfills the regulatory requirement, while continuous monitoring guides operations.
What the sensor needs to be capable of
Device SelectionThe EnoSense® RADON uses a pulse ionization chamber to measure radon levels in the range from 0 to 3,696 Bq/m³, which is many times the reference value. It also measures temperature and relative humidity, as both are needed to evaluate ventilation measures.
Unlike most sensors in the product line, it does not run on batteries. The ionization chamber requires a constant power supply; the device is powered via Power over Ethernet or 12 to 48 volts DC. This must be taken into account during electrical planning, while the measured values themselves are transmitted via EnOcean radio.
The operating temperature range is +10 to +50 degrees Celsius. For unheated basements, this is the limit that must be checked before issuing the request for proposals.
What this means for your request for proposals
8 points- Specify the measurement parameter and unit: Radon-222 activity concentration in Bq/m³.
- Specify whether the legally required annual measurement is part of the contract or will be awarded separately.
- First list the rooms in the basement and on the ground floor, including room numbers and their use.
- Specify the power supply: PoE or 12 to 48 V DC; no battery option.
- Specify thresholds and reporting path: at what value is a report sent to which system.
- Require data logging: measured values with timestamps, retention period, and output format.
- Check the operating temperature of the installation site; minimum temperature is +10 °C.
- Clarify requirements for calibrating the measuring device: Factory calibration, proof of calibration, and calibration intervals must be included in the specifications if the measurements are to be accepted by a regulatory authority.
Information current as of September 16, 2026. Regulatory information has been compiled to the best of our knowledge and does not constitute legal advice. The wording of the currently applicable version is always authoritative.
- Radiation Protection Act (StrlSchG) of June 27, 2017, Part 4, Chapter 2, Sections 121 through 132 (reference value, mandatory measurement, reporting).
- Federal Office for Radiation Protection, Information on Radon in the Workplace.
- Technical data from the EnoSense® RADON data sheet, Order No. 12904.
Would you like us to run the numbers for your building?
Send us the floor plan, dimensions, and target system. You’ll receive a recommendation for the number of units, a list of part numbers, and a quote.