DALI for Planners
DALI is the manufacturer-independent interface for lighting control, standardised in IEC 62386. For planning, the individual commands matter less than the limits of a line: how many devices it carries, how much current may flow, how long the cable can be and which generation the specification calls for.
What a DALI line can carry
Key values under IEC 62386A DALI line is a two-wire bus between a master and the control gear of the luminaires. The following values are set by the standard. They apply regardless of the manufacturer and equally to DALI and DALI-2. DALI-2 extends the functions, not the number of luminaires per line.
| Parameter | Value | What it means for planning |
|---|---|---|
| Control gear | up to 64 addresses per line | More luminaires need a second line. Keep an address plan for each line. |
| Control devices | separate address space with 64 addresses and 32 groups, from DALI-2 | Switches and sensors on the bus do not use luminaire addresses. |
| Groups and scenes | 16 groups, 16 scenes | They determine what switches together. Define them early in the lighting concept. |
| Bus current | maximum 250 mA per line, up to 2 mA per control gear | Draw up a current budget for each line. Several bus power supplies add up. Bus-powered switches and sensors count too. |
| Bus voltage | typically 16 V, permitted 9.5 to 22.5 V | Measure at the end of the cable, not only at the power supply. |
| Cable length | 300 m at 1.5 mm², maximum 2 V voltage drop | Smaller cross-sections shorten the run, to about 100 m at 0.5 mm². |
| Topology | line, star or tree, no ring | DALI has basic insulation and may run in the same cable as mains conductors. It is not safety extra-low voltage. |
| Connection | polarity insensitivity mandatory for all DALI-2 devices | Swapped wires are not an error with DALI-2 devices. For older devices, check the data sheet. |
| Data rate | 1200 bit/s | DALI carries commands, not data streams. Feedback from many devices takes time. |
| Dimming curve | 254 steps, logarithmic, 0.1 to 100 %; switchable to linear on DALI-2 LED control gear | Equal steps look even to the eye. |
| Fade time | with DALI-2 from 100 ms to 16 minutes | Long, smooth transitions can be set directly in the control gear. |
DALI, DALI-2, D4i and DALI+
Four terms that get mixed up in specificationsAll four are based on IEC 62386. They differ in what is tested and where the commands travel.
Where EnOcean comes in
Switches and sensors without a control cableThe control gear hangs on a DALI line. Switches and presence detectors normally need their own cable to a push-button coupler or to the controller. With EnOcean, this cable is not needed: the switches transmit by radio, mostly without a battery, and a controller acting as master converts the telegrams into commands on the DALI line.
Our controllers BL-201 and BL-204 are such masters. They have a built-in bus power supply of 30 mA for up to 15 control gear and connect directly to 230 V. The IP-DALI bridge AL-511-00 makes a DALI line accessible to the building management system via Ethernet and Modbus TCP. It has no bus power supply of its own, so the line needs a separate one.
Both device types are on the DALI Alliance list of control devices. If your specification requires DALI-2 certified control devices, please agree the selection with us beforehand.
What this means for your specification
8 points- Name the interface as "DALI to IEC 62386" and state whether DALI-2 certified devices are required.
- Check certification in the DALI Alliance product database, not only by the logo on the data sheet.
- Plan the lines: no more than 64 control gear per line, with reserve for later luminaires.
- Draw up a current budget for each line: total of the bus power supplies no more than 250 mA, set against the consumption of the devices.
- State cable length and cross-section for each line, 300 m at 1.5 mm².
- Define groups and scenes in the lighting concept before addressing.
- Specify addressing and commissioning as a separate service, with handover of the address plan.
- Describe the handover to the building management system separately, for example via Modbus TCP or BACnet.
Information current as of 27 September 2026. The wording of the applicable standard and the data sheet of the individual device always take precedence.
- IEC 62386-101: system requirements, including bus current, bus voltage, cabling and data rate.
- IEC 62386-102 and -103: general requirements for control gear and for control devices.
- IEC 62386-104: transmission over other carriers, the basis of DALI+.
- IEC 62386-250 to -253: bus supply in the luminaire, luminaire data, energy and diagnostics, the basis of D4i.
- DALI Alliance product database and list of control devices, www.dali-alliance.org.
- Data sheets BL-201, BL-204 and AL-511-00.
DALI, DALI-2, D4i and DALI+ are trademarks in various countries in the exclusive use of the Digital Illumination Interface Alliance. DEUTA Controls is a member of the DALI Alliance.
Are you planning lighting and sensors together?
Send us the floor plan and luminaire list. You will receive a proposal for lines, controllers and switches, with order numbers and a quote.