Specification Text · Order No. 11895, 12839, 12757

Specification Text VL-700 BASE

The complete specification item in plain text, ready to be copied into your bill of quantities—including the technical details that belong to the item. Available as a Word file with quantity and price columns alongside the text.

Text to copy

Item 1.1.1

VL-700 BASE / CE
, a Linux-based IoT edge controller with preinstalled ECS (EnOcean Control System) software

Application/TypeIoT Edge controller with optional BMS functionality
Power Supply24 V DC (10–32 V DC)
HousingDie-cast aluminum, protection class: IP20
InstallationTop-hat rail (TS35)
Dimensions134 x 102 x 45 mm
BrandDEUTA Controls GmbH
Order Numbers11895, 12839, 12757

How to include this item: The text is worded so that it can be inserted into a bill of quantities without any changes. The Word file includes the item number, quantity, and price columns.

The radio frequency depends on the country where the system will be operated, not on the purchaser’s location. Before awarding the contract, verify that the order number is appropriate for your market’s regulatory requirements.

All tender documents →

Specifications for the item

From the data sheet

These values should be included in the specifications if you want to specify the device precisely—or left intentionally open to allow for alternatives.

SystemCPU: 32-bit RISC single-core - 1 GHz
OS: Linux RT
Flash: 4 GB
RAM: 512 MB
RTC: Yes
Interfaces2x Ethernet (10/100)
1x USB (Host V 2.0, max. 500 mA)
1x Serial
1x SD card
1x expansion slot on the back (for KNX)
1x expansion slot on the back (for KNX)
SupplyInput voltage: 24 V DC (10 to 32 V DC)
Current consumption: 0.35 A @ 24 V DC
Short-circuit protection: Yes, electronic
Short-circuit fuse: Yes, electronic
Environmental ConditionsOperating temperature: -20 °C to +60 °C
Storage temperature: -20 °C to +70 °C
Humidity: 5 to 85% (non-condensing)
Protection class: IP20
Dimensions and Weight45 x 134 mm
; weight: 600 g
AccessoriesKNX Module VL-STLYE-KNX-TP (Part No.)
Installation LocationUtility room, DIN rail
Mounting HeightControl cabinet
ApprovalsEuropean Union (CE), South Korea (KC), Taiwan (BSMI)
Range, System Limits, and Mounting Heights →

Is this device suitable for your project?

Send us the floor plan, dimensions, and intended location. You’ll receive a list of devices with part numbers and a quote.