CO2 as a Control Parameter

Carbon dioxide does not measure air quality, but rather how many people are in a room and for how long. That is precisely why it is the most useful control parameter for demand-controlled ventilation.

420 ppmTypical outdoor air
1,000 ppmGuideline value from ASR A3.6
2,000 ppmThreshold for further measures
10,000 ppmEnoSense® CO₂ measurement range

What the Numbers Mean

Context

Outdoor air levels are currently around 420 ppm. Anything above that level comes primarily from the exhaled breath of the people present. A conference room with eight people and the windows closed can reach 1,500 ppm in less than an hour.

The Workplace Regulation ASR A3.6 classifies levels into three categories: below 1,000 ppm is considered hygienically safe; between 1,000 and 2,000 ppm requires ventilation; and above 2,000 ppm requires consideration of further measures. DIN EN 16798-1, on the other hand, calculates concentrations as surcharges added to the outdoor air and assigns them to categories.

The two systems are not contradictory; they address different issues. The ASR specifies when action must be taken. The DIN standard specifies the quality a room should have, and thus serves as the language of the request for proposals.

Category according to DIN EN 16798-1Supplement via outdoor airAt 420 ppm outdoorsTypical Use
Category I+ 550 ppmabout 970 ppmHigh standards, sensitive users
Category II+ 800 ppmapproximately 1,220 ppmNew construction and renovation, standard case
Category III+ 1,350 ppmabout 1,770 ppmmoderate demand, existing stock
Category IVover 1,350 ppmover 1,770 ppmacceptable only occasionally

Control Instead of Documentation

Control Engineering

Demand-controlled ventilation adjusts the airflow based on actual occupancy rather than a schedule. Under partial load—which is most of the time—this saves fan power and heating energy without compromising indoor air quality.

For this to work, the measurement must come from the occupied area, not from the exhaust air. In the exhaust air, the room air mixes with everything that enters along the way; the reading arrives too late and is too smoothed out.

CO₂ is a slow-responding parameter. After a window is opened, it takes minutes for the CO₂ level to drop. A two-point control system will therefore oscillate; a controller with a long response time that accounts for the dead time in the control loop is appropriate.

And finally: Where users are expected to ventilate the space themselves, the reading must be visible. A traffic-light system or a display in the room changes behavior; a reading in the building automation system does not.

Is this suitable for a school? Especially there: In a classroom, more people are seated in a smaller space than in an office, so CO2 levels rise more quickly, and ventilation usually comes from windows rather than a mechanical system. In that case, the display in the room isn’t just a gimmick—it’s the actual tool: It tells the class when to ventilate and lets the person in charge know afterward whether it worked. The same applies to daycare centers, lecture halls, and conference rooms.

For existing buildings, another advantage is that wireless devices don’t require new wiring—installation can be completed within a single summer break. And when classrooms are located on the ground floor or in the basement, radon must be taken into consideration; our reference project in this area is a university with 70 monitored areas.

LocationIn the living area1.2 to 1.8 m above the floor, not next to the door, not in the supply air stream, and not in the exhaust air.
ControlSlow rather than sharpCO₂ levels lag behind occupancy changes. A controller with a long response time maintains a more stable value than a switch-off threshold.
VisibilityTraffic light or displayWhere the system is controlled by occupancy, the value should be displayed in the room—either as a colored traffic light or as a number on a room display.

How accurately does a CO2 sensor measure?

Selection

The EnoSense® CO2 covers a range of 0 to 10,000 ppm and also measures temperature and relative humidity. It is powered by a solar cell and two AAA batteries, which are included. The EnoPuck® CO2 covers a range from 0 to 2,550 ppm, features individually dimmable RGB LEDs arranged like a traffic light, and is powered by a plug-in power supply.

The EnoSign® CO2/Temp/rH displays the readings from any sensor in the system without taking measurements itself and without requiring a connection. This is the model for rooms where the measurement location and the display location are not the same.

How accurately the sensor measures: Typically, the error is ±30 ppm plus 3 percent of the measured value, with a guaranteed maximum of ±45 ppm plus 3 percent; these specifications are listed in the device’s data sheet. At 1,000 ppm, this typically amounts to about 60 ppm and at most 75 ppm—sufficiently accurate for making a ventilation decision, but a figure worth knowing when comparing two sensors in the same room.

Regarding calibration: Automatic recalibration is not enabled on our sensors. Calibration is intentionally initiated on the device itself using the service button; the procedure is described in the manual, and there are short videos available as well. This should therefore be included in the maintenance schedule—and, for rooms that are never ventilated, in the design specifications.

The measurement range and requirements are well-matched. For monitoring an office, 2,550 ppm is sufficient. Where peak values need to be documented, the wider range is the safer choice.

How many CO2 sensors do I need?

Density and Installation

The number of CO2 sensors required for a given area can be determined rather than estimated: Two international standards specify a density of measuring devices, and both result in figures of the same order of magnitude. For an open-plan office measuring 200 square meters, this translates to one device —as a minimum requirement.

WELL v2 requires, in Feature A08, at least one sensor per 3,500 square feet of usable floor area, or approximately 325 square meters. RESET Air for Commercial Interiors takes a different approach: one sensor per regularly used room type, with an additional limit of 500 square meters of coverage per sensor. A meeting room therefore counts as a separate unit, even if it is small.

The lower limit is therefore not the answer for every area. Where the use of a space varies—such as a meeting area, break room, or reception area—each constitutes a separate zone and should be measured individually. Therefore, plan for one device per usage zone and check the area limit as a second condition.

Regarding accuracy: WELL requires 10 percent CO2 at 750 ppm. The EnoSense® CO2 also meets this requirement, with a maximum value of 9.0 percent and a typical value of 7.0 percent. It also meets the measurement interval requirement of no more than ten minutes, with a measurement interval of five minutes. You can find the complete line-by-line verification against both standards here: WELL and RESET in Detail →

SpecificationWELL v2, Feature A08RESET Air CI v2.0
DensityOne device per 325 m² (3,500 ft²) of usable floor spaceOne device per room type, with a maximum coverage area of 500 m² per device
Installation height1.1 to 1.7 m above the finished floor0.9 to 1.8 m, on the wall and in the center of the room
DistanceAt least 1 m from doors, openable windows, and supply or exhaust air ventsAt least 5 m from openable windows, filters, and supply air inlets
Measurement intervalNo more than 10 minutes for CO2Continuous, with data transmitted to the analysis system
CO2 Accuracy10 percent at 750 ppmOnly accredited Class A or B instruments
Additional requirements of the standards: Neither standard can be met with CO2 alone. WELL A08 requires at least three of the seven listed parameters; our devices do not measure particulate matter or VOCs. RESET Air requires PM2.5 and TVOC and only permits accredited measuring devices that RESET lists in its own directory. Regardless of this, however, the standards remain the best benchmark for density, installation, and testing intervals—even for a project that is not seeking certification.

What this means for your request for proposals

8 points
  • Specify the target category according to DIN EN 16798-1 instead of a raw ppm value.
  • Specify the measurement range and accuracy appropriate for the room’s requirements—typically ±30 ppm plus 3 percent of the measured value.
  • Specify CO₂ calibration as a maintenance service: It is initiated on the device and does not run automatically—this is particularly important for rooms that are never ventilated.
  • Specify the measurement location for each room: height, distance from the door, supply air, and windows.
  • Specify the density of measuring devices: one device per usage zone, with an area limit of 325 m² as per WELL A08 or 500 m² as per RESET Air.
  • Define thresholds and their effects: airflow rate, alert, and in-room display.
  • Specify whether a visible display or traffic light is required in the room.
  • Specify power supply: solar with battery or AC adapter.
Status and Sources

Information current as of September 16, 2026. Regulatory information has been compiled to the best of our knowledge and does not constitute legal advice. The text of the currently applicable version is always authoritative.

  • Technical Regulation for Workplaces ASR A3.6 “Ventilation,” Assessment of Carbon Dioxide Concentration.
  • WELL v2, Feature A08 “Air Quality Monitoring and Awareness,” Part A08.1, Version Q4 2021: Density, Installation, Interval, and Accuracy.
  • RESET™ Air Standard for Commercial Interiors v2.0 dated January 31, 2018, Sections 2.2.6 (Installation) and 2.2.7 (Calculation of the Number of Units, Coverage Area 500 m²).
  • DIN EN 16798-1, Indoor air quality categories based on the outdoor air concentration supplement.
  • Measurement ranges from the EnoSense® CO2 and EnoPuck® CO2 data sheets.